OHA Drinking Water Services
Contact Report Details |
|||
| PWS ID: | OR41 00236 | ||
| PWS Name: | COTTAGE GROVE, CITY OF | ||
| Who Was Contacted and Phone: | Ray Pardee (541) 942-7064 | ||
| Contact Date: | 10/20/2009 | ||
| Contacted By: | LYON, CASEY (REGION 2) | ||
| Contact Method/Location: | Office | ||
| Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
| Reasons: | Operations None |
||
| Details: | SUMMARY: Laying creek turbidity exceedance DETAILS: Ray Pardee reported to me that on 10/15/09 the Laying Creek WTP had a polymer feed pump failure and that Individual filters exceeded 1 NTU from about 1:15 am to 4:45 am. The feed pump was eventually repaired. The highest individual filter reading was 1.97 NTU. The CFE did not exceed 1 NTU. ACTION NEEDED: no other action required at this time. | ||