OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 92681
PWS Name: USFS WHISKEY SPRINGS
 
Who Was Contacted and Phone: Chuck Coleman (541) 560-3405
Contact Date: 09/08/2009
Contacted By: OBEREIGNER, MIKE (JACKSON COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Repeat coliforms positive DETAILS: Samples collected 9/3/09. Alert issued - 9/08/09 I spoke with Scott Beemer regarding the repeats. He says that he has already shut the system down to users and chlorinated the tank and distribution system. He will allow 24 hours contact time then flush the system out until 0ppm chlorine - he has a chlorine test kit. A special sample will be collected and Scott will call me after he learns of the results. I emailed Scott a tier 2 public notice template. 9/14/09 - Scott Beemer called and informed me that a special sample collected on 9/10/09 came up negative. He said the system was shock chlorinated on the 9/9/09 and completely flushed and a chlorine residual of zero ppm was determined using hi Hach chlorine test kit. I advised him that the state protocol for sampling after shock chlorination is to wait five days after no chlorine is detected. Scott says that the USFS requires four repeats to be collected at this time: I advised him to have them marked special so that they are not confused with the repeat samples collected on 9/3/09. I reminded Scott that five temporary routines are due in October ACTION NEEDED: Five temporary routines are to be submitted in October.
 
Associated Alerts: COLI6721 - 09/08/2009 - COLIFORM (TCR)

COLI6721 - 09/08/2009 - COLIFORM (TCR)

COLI6721 - 09/08/2009 - COLIFORM (TCR)



More information for this water system: SDWIS ID 1229
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login