OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00540
PWS Name: MONROE, CITY OF
 
Who Was Contacted and Phone: Jeff Houchin (541) 451-1117
Contact Date: 12/07/2009
Contacted By: PARMENTER, AMY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
Operations
 
Details: SUMMARY: DBP MCL Exceedance DETAILS: Monroe exceeded the RAA for TTHM with their 4th quarter 2009 sample. The result was 0.0969 mg/L, with a RAA of 0.110 mg/L. Monroe has already issued public notice and will be reissuing it this week. The system has increased reservoir turnover, decreased chlorine residual, and increased hydrant flushing, but none of these has yet to decrease the DBP levels. The system recently installed a coagulant to their membrane system and has submitted the plans for Plan Review. The system now has three quarters of results for their new surface water source, and the RAA has exceeded 0.064 mg/L for TTHM and 0.048 mg/L for HAA5-- therefore, Disinfection Profiling is required. I will get Disinfection Profiling guidance to them soon, but they will not have a years worth of data for the surface water source until February. ACTION NEEDED: Get copy of reissued Public Notice from Monroe. Send them Disinfection Profiling information. Await Plan Review for the coagulant.
 
Associated Alerts: CHEM3841 - 11/25/2009 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM

CHEM3841 - 11/25/2009 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM



More information for this water system: SDWIS ID 3364
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login