OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 05246 | ||
PWS Name: | PGE BEAVER GENERATING STATION | ||
Who Was Contacted: | Erica Amt | ||
Contact Phone: | (Email address hidden) | ||
Contact Date: | 08/24/2020 | ||
Contacted By: | FARRELLY, PETER (DWP) | ||
Contact Method/Location: | |||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | VOCs |
||
Details: | Another ethylbenzene & xylene detection. Remain on quarterly monitoring. WS will sample both at the EP and at their raw intake (i.e., before and after the 2019 water treatment system upgrades) to see if there are any detections in the raw water. These were slight detections at 5 ppb for ethylbenzene. The MCL is 700 ppb. 52 ppb for xylene. The MCL is 10,000 ppb. Next sample is slated for October. |
||
Associated Alerts: | CHEM9027 - 08/21/2020 - ETHYLBENZENE , XYLENES, TOTAL See also: 02/19/2021 |