OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00703 | ||
PWS Name: | RICHLAND, CITY OF | ||
Who Was Contacted and Phone: | Gary Chamberlin (541) 540-6141 | ||
Contact Date: | 03/22/2010 | ||
Contacted By: | BURNETT, GARY (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
Reasons: | Lead or Copper Lead/Copper |
||
Details: | SUMMARY: Water quality parameters completed due to copper action level exceedance. DETAILS: Water quality parameters for the Entry Point were reported by Magic Valley Labs. Alkalinity 160 mg/l, hardness 110 mg/l, field pH 7.8. Based on the parameters, the DIC is 40. Five copper samples were also taken and the highest result was 0.38 mg/l. These sites were evaluated and determined to be valid sites. ACTION NEEDED: Five more copper samples to be taken in June-July to substantiate that approved sites are consistently below the action level. |