OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 05592 | ||
PWS Name: | BOB BELLONI RANCH | ||
Who Was Contacted and Phone: | Jim Pinson (541) 290-9931 | ||
Contact Date: | 07/07/2010 | ||
Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
Contact Method/Location: | Field | ||
Assistance Type: | VIOLATION RESPONSE | ||
Reasons: | SWTR N/A |
||
Details: | SUMMARY: Review treatment system and ID cartridge filters DETAILS: Treatment is settled water, manganese/iron removal (Macrolite), cartridge roughing filter, cartridge pre-filter, and 1 micron cartridge main-filter in series. The pre- and main-filter housings are a 3M product that is not approved. The filters are obtained from ISC Sales of Plano, Texas and are not approved. A list of approved filters was provided to Jim, and he is pursuing the Rosedale device. Jim also asked about nitrate sampling frequency. ACTION NEEDED: Send letter with plan review process and nitrate sampling frequency. |