OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00725
PWS Name: MCNULTY WATER PUD
 
Who Was Contacted: Shannon Tice
Contact Phone: 503-397-1301
Contact Date: 09/18/2020
Contacted By: OSBORN, DANIEL (COLUMBIA COUNTY)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Arsenic
 
Details: I spoke with Shannon Tice about McNulty Water PUD's most recent Arsenic water sample results. Both of them in SDWIS/Data Online say they're from EP-D for Robinette Well, but one is above the MCL for Arsenic, and the other shows ND - none detected.
Shannon says that the first sample with the Arsenic MCL exceedance was taken directly from the ASR - aquifer storage and recovery location, while the second sample with the Arsenic non-detect results was taken from the Reservoir location nearest the Robinette well. So even though they're listed both as EP-D for Robinette Well, they're technically 2 different nearby locations.
She says, as she understands it, the sources are blended together in the Reservoir to bring the Arsenic levels down through dilution before going out to the public, and that's why the second sample results were most likely to be non-detect for Arsenic.
McNulty's Arsenic situation at that entry point has been an ongoing issue and I have been discussing with State DWS on the next steps of whether Arsenic treatment will need to be required or not.
 
Associated Alerts: CHEM9065 - 09/18/2020 - ARSENIC   See also: 09/18/2020

CHEM9058 - 09/15/2020 - ARSENIC



More information for this water system: SDWIS ID 3402
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login