OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 05798 | ||
PWS Name: | SUNRIDGE WATER INC | ||
Who Was Contacted and Phone: | Jerry Tremblay (541) 567-6505 | ||
Contact Date: | 10/27/2010 | ||
Contacted By: | GOSS, BILL (DWP) | ||
Contact Method/Location: | Field | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Coliform N/A |
||
Details: | SUMMARY: Collected Repeat Samples DETAILS: Received alert for one of the samples that Jerry had collected on 10/20. The sample tested positive for total coliform, however I observed that Jerry had set the cap down while filling the sample bottle. A sample I collected at the same site immediately after Jerrys tested absent for TC. Met Jerry onsite to collect the required repeat samples. Also met with Brady Rettkowski who was working on replacing the DCVA on the well no. 2 discharge line with a single check valve. ACTION NEEDED: DWP to invalidate the TC positive routine sample collected 10/20 due to improper sampling procedure. | ||
Associated Alerts: | COLI8499 - - |