OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00205 | ||
PWS Name: | COOS BAY NORTH BEND WTR BRD | ||
Who Was Contacted and Phone: | Robert Buras (832) 226-2365 | ||
Contact Date: | 12/22/2010 | ||
Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
Reasons: | SWTR None |
||
Details: | SUMMARY: IFE must be used for compliance reporting DETAILS: After discussing the turbidity monitoring plumbing, it is clear that the IFEs turbidity sample lines are combined to feed the CFE turbidimeter. This is not an accepted practice. The options are to reconfigure to get a true CFE turbidity sample (which is not physically possible in the current system configuration) or to report the highest 4-hour IFE reading on the monthly SWTR compliance turbidity report. ACTION NEEDED: send e-mail to system |