OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 91243 | ||
PWS Name: | KELLYS | ||
Who Was Contacted and Phone: | Kathy Kelly (541) 938-4247 | ||
Contact Date: | 03/03/2011 | ||
Contacted By: | BAKER, AMY (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | PLAN REVIEW | ||
Reasons: | GWR Operations |
||
Details: | SUMMARY: field visit for chlorinator DETAILS: Due to confirmed contamination in the water source, the system was required to install chlorination as an interim measure until a new water source can be determined. John Kerns, Pendleton Electric, installed the unit on 03/03/11. The unit is: Stenner feed pump system - model ID# 85MJH1A1STAA. It cycles off and on with the domestic pump on the well. Sodium Hypochlorite is used. At the time of the visit, the chlorine residual was a 1.0 ppm. System is to take daily measurements and document on the provided form. Form is to be turned in monthly. ACTION NEEDED: Order chlorine test kit (currently system is borrowing space DWP kit) and measure residual daily. Residual is to be maintained at a minimum of 0.2 ppm. |