OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05246
PWS Name: PGE BEAVER GENERATING STATION
 
Who Was Contacted and Phone: Bob Reller (503) 728-7204
Contact Date: 08/02/2011
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
N/A
 
Details: SUMMARY: Response to high turbidity values DETAILS: Bob and I spoke about the 1-2 NTU values observed on 7/26 and 7/27 that were taken at the port located after 50,000 storage tank, carbon filter and 600 gallon hydropneumatic tank. I explained that filter effluent turbidity values need to be taken right after filter prior to any storage and that these NTU values after storage were not to be used to assess filter performance and consideration with the turbidity MCL. I explained that these high values are reflective of random events in distribution and should not be used for MCL compliance and possible boil water notice. I instructed Bob to immediately install sample port right after filters to measure combined effluent turbidity. Bob will install combined port prior to storage. In interim, PGE will meaure and record highest of the four individual filter effluent readings on monthly form reported to DWP. ACTION NEEDED: PGE to inform DWP when change to combined filter effluent sample port is made. DWP to provide support to Columbia County and system to address SWTR requirements.


More information for this water system: SDWIS ID 4162
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login