OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 93718
PWS Name: NINETY-ONE ELEM SD 91
 
Who Was Contacted and Phone: Wayne Layman (503) 266-7861
Contact Date: 04/21/2011
Contacted By: HENRY, ROBERT (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: Arsenic Removal DETAILS: The Canby School District operates a small water system serving the Ninety-One Elementary School. System has a primary well that feeds the distribution system which provides drinking water to approximately 455 students and staff. The system is composed of a primary well and an emergency well that feeds the distribution system. In 2001, the EPA lowered the Maximum Contaminate Limit (MCL) on arsenic from 0.050 mgl to 0.010 mgl (compliance was required by 2006). The most recent test of the raw water reported 0.017 mgl. I coordinated with school and treatment plant manufacturer regarding recommendations for co-precipitation/filtration of arsenic. I finalized report recommending co-precipitation/filtration and met with school district personnel to recommend next steps to achieve compliance. ACTION NEEDED: None needed at this time.


More information for this water system: SDWIS ID 1422
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login