OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 93461 | ||
PWS Name: | BREITENBUSH HOT SPRINGS | ||
Who Was Contacted and Phone: | Dean Terry | ||
Contact Date: | 06/16/2011 | ||
Contacted By: | BAIRD, GREGG (REGION 1) | ||
Contact Method/Location: | Office | ||
Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
Reasons: | SWTR Chlorine |
||
Details: | SUMMARY: Failure to meet EP disinfection DETAILS: Low chlorine level on 6/15 caused inadequate disinfection of systems drinking water. Chlorine pump was set too low. Needed chlorine residual of 0.48 ppm to meet CTs, dropped to 0.3 ppm-- chlorine pump was adjusted and reservoir was shocked to bring residual up to 1.1 ppm. ACTION NEEDED: System did a tier 2 public notice notifying users of treatment interruption. |