OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 93461
PWS Name: BREITENBUSH HOT SPRINGS
 
Who Was Contacted and Phone: Dean Terry
Contact Date: 06/16/2011
Contacted By: BAIRD, GREGG (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
Chlorine
 
Details: SUMMARY: Failure to meet EP disinfection DETAILS: Low chlorine level on 6/15 caused inadequate disinfection of systems drinking water. Chlorine pump was set too low. Needed chlorine residual of 0.48 ppm to meet CTs, dropped to 0.3 ppm-- chlorine pump was adjusted and reservoir was shocked to bring residual up to 1.1 ppm. ACTION NEEDED: System did a tier 2 public notice notifying users of treatment interruption.