OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 95139 | ||
PWS Name: | MONMOUTH KINGDOM HALL | ||
Who Was Contacted and Phone: | Zach Erdman (503) 871-4533 | ||
Contact Date: | 01/13/2012 | ||
Contacted By: | FARRELLY, PETER (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | PLAN REVIEW | ||
Reasons: | Coliform None |
||
Details: | SUMMARY: Assessment sampling of unconfined well with UV treatment and nearby septic field DETAILS: These are corrections/amendments of previous contact report Zach measured the following setback distrances: 144 from well head to septic tank/pump Also, the WS uses the Hallet 15XS-- an NSF 55 class A certified UV unit that is not validated to appropriate, post-2009, standards. Therefore, no inactivation credit is granted. |