OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05246
PWS Name: PGE BEAVER GENERATING STATION
 
Who Was Contacted and Phone: Bob Reller (503) 728-7004
Contact Date: 04/05/2012
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
Operations
 
Details: SUMMARY: SWTR assistance - elevated turbidity DETAILS: Bob called to report that PGE Beaver had elevated NTUs due to a coagulant dosing problem. From about 920 a to 10 a on 4/5, system spiked up to 1.165 NTU. The sand filter was backwashed around 11 am, and the filter plant turned off at 1115 am. Systems chlorine residuals > 1 ppm and CTs met during this time (CT of 59 with CT required of 44), with detectable chlorine residual in the distribution system - around 1.2 mg/L. I indicated that the maximum turbidity MCL is 1 MCL, (1.49 with significant digits), so given the resolution on PGEs Combined chart recorder the actual MCL had not been exceeded, and no boil water notice is necessary at this time. System will be taking off plant for some time (week or two) and Bob will inform me when treatment plant back on-line again. ACTION NEEDED: DWP to support PGE Beaver in filling out April monthly surface water reporting form for NTU and CTs.


More information for this water system: SDWIS ID 4162
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login