OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05364
PWS Name: MT TERRACE MHP
 
Who Was Contacted and Phone: Rob Henry
Contact Date: 04/17/2012
Contacted By: MACPHERSON, JAMES (REGION 2)
Contact Method/Location: Office
 
Assistance Type: PLAN REVIEW
Reasons: SWTR
Operations
 
Details: SUMMARY: Tracer study proposal DETAILS: Physical configuration of system will result in pulsed draw from the wells due to a booster pump that is almost an order of magnitude more powerful than the well pumps. There is a 900 gallon reservoir floating on the system that will likely drive the periodicity of the booster pump. This is OK as it is how the system operates. A key data acquisition will be flow rate during the tracer study. Flow needs to be more than 27 gpm, and optimally between 36 and 46 gpm. ACTION NEEDED: none