OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 91959 | ||
PWS Name: | OPRD HB VAN DUZER STATE PARK | ||
Who Was Contacted and Phone: | Jon Moll (541) 994-7341 | ||
Contact Date: | 05/31/2012 | ||
Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
Reasons: | SWTR Operations |
||
Details: | SUMMARY: Alternatives to achieve sufficient treatment credit DETAILS: Would UV addition provide sufficient treatment credit? Verified UV devices can provide at least 3.5-log treatment. Conceivably UV could be added after the existing membrane filter to meet the treatment credit required and provide multiple barriers. If the membrane filter did not have a daily direct integrity test, it would not receive treatment credit. However, with a construction waiver it might provide the necessary multiple barrier component while UV provides the needed 3.0-log treatment credit against Cryptosporidium and Giardia. (Used equipment requires explicity approval from the department.) ACTION NEEDED: none |