OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00482 | ||
PWS Name: | HILAND WC - BEAR CREEK | ||
Who Was Contacted and Phone: | Chad McMurry | ||
Contact Date: | 05/30/2012 | ||
Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
Contact Method/Location: | Office | ||
Assistance Type: | PLAN REVIEW | ||
Reasons: | SWTR Operations |
||
Details: | SUMMARY: Pilot testing membrane unit DETAILS: Is it appropriate to pilot test a Seccua membrane filter using the Virex Pro model when the Phoenix model would be used if selected? Yes, the membranes are the same material and the control systems are essentially the same. The primary information to gain from this pilot test is whether and what pre-treatment would be needed. This information would not be significantly affected by the difference in physical configuration and flow rate of the respective models. Additionally there does not appear to be a concrete slab under the redwood tank. Lastly, the maximum operating volume will be provided in future. ACTION NEEDED: none |