OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 92106
PWS Name: UMPQUA RIVER INN & SUITES
 
Who Was Contacted and Phone: Rod Edel
Contact Date: 04/23/2012
Contacted By: GROSS-REGAN, CAROLINE (DOUGLAS COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Positive repeats Ecoli in distribution source positive for coliform additional repeat positive coliform DETAILS: This system does not chlorinate, has no reservoirs, does have pressure tanks. Discussed process to follow after positive repeats for Ecoli. Sent template for boil water notice posting requirements and requirement to send to the state. Notify patrons of Ecoli positive. He may close facility as use is very low at this time of year. ACTION NEEDED: Post public notice today Tier 1 exceeds mcl for fecal coliform. Send copy of notice to state. Inform all patrons not to drink or brush teeth with water. Disinfect well. After the process is complete, make sure there is 0 ppm chlorine detected before taking any samples. Mark these samples special. If they are negative, boil water notice may be removed. If positive, need to investigate reason for the coliform occurrence. Need to take 5 temporary routines in May
 
Associated Alerts: COLI10425 - 04/23/2012 - COLIFORM (TCR) , E. COLI

COLI10425 - 04/23/2012 - COLIFORM (TCR) , E. COLI

COLI10425 - 04/23/2012 - COLIFORM (TCR) , E. COLI

COLI10425 - 04/23/2012 - COLIFORM (TCR) , E. COLI

COLI10425 - 04/23/2012 - COLIFORM (TCR) , E. COLI

COLI10425 - 04/23/2012 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 1157
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login