PWS ID: OR41 00799
PWS Name: SEASIDE WATER DEPARTMENT
 
Who Was Contacted and Phone: Ben Davis (503) 738-5112
Contact Date: 07/11/2012
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: SOCs
N/A
 
Details: SUMMARY: Response to SOC detect DETAILS: I spoke to Ben abou the 4/25/12 detect of di (2-ethyl hexyl phthalate) of 0.0017 mg/L, almost 3 times the detection level of 0.0006 mg/L, but below MCL of 0.006 mg/L. I explained that City needs to begin quarterly monitoring for constituent with a first sample during third quarter 2012. I explained compliance with the MCL is determined by a running annual average. Ben not aware of reason for detect as previous samples all non-detect, but may contact lab to follow up. ACTION NEEDED: City to begin quarterly monitoring for 2-ethyl hexyl phthalate 3rd quarter 2012. DWP to review results after 4 consecutive quarters for seasonal variability, compliance with the MCL or if frequency may be reduced given results reliably & consistently below MCL. DWP to offer support to City.
 
Associated Alerts: CHEM5419 - 07/10/2012 - DI(2-ETHYLHEXYL) PHTHALATE



More information for this water system: SDWIS ID 4303
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login