OHA Drinking Water Services
Contact Report Details |
|||
| PWS ID: | OR41 00672 | ||
| PWS Name: | POWERS, CITY OF | ||
| Who Was Contacted and Phone: | Paul Strader (541) 404-6117 | ||
| Contact Date: | 08/03/2012 | ||
| Contacted By: | MACPHERSON, JAMES (REGION 2) | ||
| Contact Method/Location: | Office | ||
| Assistance Type: | OTHER REGULATORY - REGULATORY ASSISTANCE | ||
| Reasons: | SWTR None |
||
| Details: | SUMMARY: Required CT values DETAILS: Use the required CT look-up table that is for the lower temperature. If the temperature is 14.9 C, then the 10 C table should be used. If the temperature is 15.0 C, then the 15 C table should be used. Always round the temperature DOWN to the next lowest value in the look-up tables. (pH gets rounded UP) ACTION NEEDED: none | ||