OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 95397 | ||
PWS Name: | UPPER COLUMBIA MILL | ||
Who Was Contacted and Phone: | Laura Hofbauer w/ KUO Lab (541) 922-6435 | ||
Contact Date: | 08/03/2012 | ||
Contacted By: | GOSS, BILL (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Nitrate N/A |
||
Details: | SUMMARY: Nitrate Alert Response DETAILS: Received alert for nitrate result of 13.8 mg/l from sample collected 7/16/12. Spoke with Laura at KUO Lab who collected the sample. The high result was from a raw water sample collected before the RO treatment units. Nitrate samples were collected the same day after each of the two RO units at the designated potable taps in the breakrooms. Both tested well below the MCL. These results appear on Data Online. ACTION NEEDED: none. | ||
Associated Alerts: | CHEM5466 - 08/03/2012 - NITRATE , SODIUM CHEM5466 - 08/03/2012 - NITRATE , SODIUM |