OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95496
PWS Name: PANAMERICAN BERRY GROWERS
 
Who Was Contacted: Angela Cervantes
Contact Phone: 503-390-5612
Contact Date: 12/04/2020
Contacted By: TEAMUS, JOSHUA (DEPT OF AGRICULTURE)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Nitrate
 
Details: I spoke with the operator of PBG water system regarding the most recent nitrate samples. The system is assigned to take a single nitrate sample per year from the entry point of each well. This means after treatment and before any blending together of the two sources.

Both wells produced results at their respective entry points above the alert level of 50% of the 10 ppm MCL. I provided information regarding the chronic and acute health hazards of nitrate via email subsequent to the call.

There appears to be fluctuation in the levels of nitrate from these wells. Results as high as 14ppm and as low as <1ppm have been reported. We discussed examining seasonality of result levels. Differences based on season could be related to the weather, neighboring uses of groundwater or recent average rate of groundwater extraction.

This business has periods of the year with much higher water usage. The operator seemed interested in taking tests during different quarters in future years.

We also discussed methods of nitrate reduction including blending and ion-exchange.
 
Associated Alerts: CHEM9156 - 12/03/2020 - NITRATE



More information for this water system: SDWIS ID 5314
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login