Who Was Contacted and Phone: Leun Soo Lee (503) 826-0777
Contact Date: 08/06/2012
Contacted By: WIDDICOMBE, KENT (DEPT OF AGRICULTURE)
Contact Method/Location: Field
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Coliform
Chlorine
 
Details: SUMMARY: Regulatory Assistance DETAILS: Received letter dated 6/27/12 that the DWP had received a water sample from the system listed as deactivated. I visited site, operator stated owner since 2007, still operating store, even though new AG license issued in April 2011. The sample received on June 22/2012 is a routine quarterly sample that is treated with residual chlorination. The system has contracted with a lab to take residual samples, and takes chlorine levels only when chlorine tank is filled with NSF chlorine. The chlorinator is a flow based system that feeds into the water line as it exists the pressure tank into the supply line-- the chlorine mix tank was almost empty. There is a flowmeter, pressure switch, pressure gauge at 60 psi, floor drain, and NFS Bleach (EPA#10897-26 HBSB Multi-Chlor), and the pitiless adaptor does not appear to have a screened vent. There faucet to drain the tank, appears to be able to be used as a raw water tap. ACTION NEEDED: The system is not recording chlorine residuals, has not been taking quarterly coliform samples since September 2010, and so now taking quarterly coliform samples beginning June 22. 2012. Discussion recording daily chlorine residuals, taking annual raw water sample, annual nitrate sample, and one time arsenic sample.


More information for this water system: SDWIS ID 2305
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login