OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00970
PWS Name: NESKOWIN REG WATER DIST
 
Who Was Contacted: Troy Trute
Contact Phone: 541-992-1655 (Email address hidden)
Contact Date: 12/18/2020
Contacted By: HOFELD, EVAN (DWP)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
 
Details: Hi Troy,
I received a call from Troy Trute to let me know that their last quarterly DBP sampling completed 12-2-2020 had an individual TTHM result of 0.083 mg/l. Although the individual TTHM result is 0.083 mg/l, this did not result in an exceedance of the 0.080 MCL, which is determined based on the locational running annual average (LRAA) of results over the past 4 quarters. This also did not result in an exceedance of the 0.080 Operational Evaluation Level (OEL). No further action is required at this time, but I let Troy know to be sure to include the result in the range of DBP results reported in the Consumer Confidence Report (CCR) for calendar year 2020. I sent a follow-up e-mail on 9-18-20 and again on 9-22-20 with information about automatic flushing and chlorine hold studies that may help with managing DBP formation. Troy indicated that in early 2021, they were going to start feeding ACH coagulant ahead of the membrane filters to reduce soluble TOC.
 
Associated Alerts: CHEM9173 - 12/18/2020 - TTHM



More information for this water system: SDWIS ID 4004
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login