OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 94912 | ||
PWS Name: | DOUGLAS CO PKS - KANIPE MEMORIAL | ||
Who Was Contacted and Phone: | Gary Groth (541) 440-4302 | ||
Contact Date: | 02/12/2013 | ||
Contacted By: | STEWART, SHELLEY (DOUGLAS COUNTY) | ||
Contact Method/Location: | Office | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Coliform N/A |
||
Details: | SUMMARY: 3 of 5 temporary routines positive for coliform DETAILS: Jon indicates they treated the underground reservoir but the sample taken did not draw from the treated water only from a pressure tank that doesnt draw from the reservoir until the PT is nearly empty. Suggestions were made regarding interim measures prior to next months round better protecting the tank inlets from surface intrusion, re treating the tank. They are planning on cleaning out the tank in march. Tier 2 notice is still up. He was instructed to reference the sampling schedule page for what is still expected. ACTION NEEDED: Await next months sample results. | ||
Associated Alerts: | COLI11488 - 02/06/2013 - COLIFORM (TCR) COLI11488 - 02/06/2013 - COLIFORM (TCR) COLI11488 - 02/06/2013 - COLIFORM (TCR) |