OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00217
PWS Name: LAUREL ACRES WATER CO INC
 
Who Was Contacted and Phone: Leo Jones (503) 969-4415
Contact Date: 02/19/2014
Contacted By: FEDERICO, JOSEPH (WASHINGTON COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Positive Ecoli DETAILS: I contacted Gregg Baird and asked if the system needed to do source testing or just 4 repeats in distribution. Gregg checked and left message that they only need to do the 4 repeats no source test. I contacted Leo and asked what happened. Eh said there was air in the chlorinator line which he fixed. He said yesterdays test was over 0.20ppm at his home. He usually maintains 0.30. He immediately checked the chlorinator today when he tested 0.10 at the home. He said the lab took the sample upstream and noted 0.00ppm. He thinks they still had residual in the system the entire time but not a min of 0.20ppm He issued a boil water notice to all users already., He will take 4 repeats as soon as possible in the distribution. He tested the residual in his home 1 hour ago and had 0.30ppm. Leo will keep boil notice in place until test results come back ok. I spoke to Gregg and discussed incident. I contacted Leo and he said he is picking up the sample bottles today and will have samples in to the lab by tomorrow morning. I reminded Leo minimum residual is 0.30ppm for chlorine ACTION NEEDED: none
 
Associated Alerts: COLI12623 - 02/19/2014 - COLIFORM (TCR) , E. COLI

COLI12623 - 02/19/2014 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 3272
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login