OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05683
PWS Name: ODFW IRRIGON FISH HATCHERY
 
Who Was Contacted and Phone: Marc Garst (541) 922-5732
Contact Date: 02/14/2014
Contacted By: GOSS, BILL (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Nitrate
N/A
 
Details: SUMMARY: Nitrate Alert Response DETAILS: 2/14/14 - Received alert for nitrate result of 11.5 mg/l collected 1/28/14 at house 5 pou unit. Spoke with Marc. Directed him to contact that homes occupant with nitrate public notice info. The RO units had been serviced shortly before the samples were colected. Results from the other five homes tested under the MCL. Marc will collect a follow up sample at the home that failed, and also an untreated source sample. 2/21/14 - Received results from follow up samples. Sample at the home tested at 14.4 mg/l and the source sample tested at 40.9 mg/l. Marc will contact the RO unit manufacturer to see what advice they can offer. 3/11/14 - Spoke with Marc. The manufacturer suggested the membrane may not have been broken in properly before the samples were collected. The membrane in the unit that failed was replaced, and is having water flushed through according to the manufacturers recommendations. Another sample from the unit will be collected 3/13/14. ACTION NEEDED: Further action to be based on next sample results.
 
Associated Alerts: CHEM6205 - 02/14/2014 - NITRATE

CHEM6205 - 02/14/2014 - NITRATE

CHEM6205 - 02/14/2014 - NITRATE

CHEM6205 - 02/14/2014 - NITRATE

CHEM6205 - 02/14/2014 - NITRATE

CHEM6205 - 02/14/2014 - NITRATE



More information for this water system: SDWIS ID 2471
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login