OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95495
PWS Name: FULCRUM DINING
 
Who Was Contacted and Phone: Chad hahn (541) 226-8490
Contact Date: 03/28/2014
Contacted By: JENSEN, NEIL (LINCOLN COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Nitrate
N/A
 
Details: SUMMARY: Nitrate 6.74 mg/L DETAILS: Chem alert for nitrate greater or equal to 50% of MCL of 10.0mg/L. Left message and then spoke to Chad regarding increase monitoring frequency required for nitrate from yearly to quarterly. Informed him the next sample for nitrate will be due in 2nd quarter of 2014 and will need to be tested for at least 3 consecutive quarters. Discussed health implications of nitrate in drinking water and traditional causes for increased levels found in drinking water. He stated he will collect nitrate samples when coliform sample are collected quarterly. ACTION NEEDED: I will follow up in may to ensure nitrate test has been collected or is planned to be collected.
 
Associated Alerts: CHEM6251 - 03/27/2014 - NITRATE



More information for this water system: SDWIS ID 5313
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login