OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 01203 | ||
PWS Name: | AVION WC - RED CLOUD | ||
Who Was Contacted and Phone: | Gene Hubbard (541) 948-6676 | ||
Contact Date: | 08/26/2014 | ||
Contacted By: | GOSS, BILL (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | BOIL WATER | ||
Reasons: | Operations N/A |
||
Details: | SUMMARY: System to Remain on Boil Order DETAILS: Gene called with results of the samples collected Monday after pressure was restored. Six samples were collected from three locations with one set run using MTF method and the other set using Colilert. The MTF sample results were still pending, but two of the three samples run with Colilert tested positive for total coliform. I told Gene that the boil order must remain in effect until all samples test absent for coliform. Gene said he plans to chlorinate and flush the system, then collect another set of samples after there is no detectable chlorine residual. ACTION NEEDED: System to remain on boil order. |