OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00433
PWS Name: COVE POINT CORPORATION
 
Who Was Contacted and Phone: Anne Wenner
Contact Date: 10/02/2014
Contacted By: BELL, DELBERT (KLAMATH COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Follow up on Total Coliform Positive Temporary Routine Sample taken 9-25-14. DETAILS: One of five temporary routine coliform samples taken 9-25-14 was positive. I went out to the system this morning and talked with the treasurer (Anne Wenner). Anne and I took chlorine residual readings at two houses-- one had no residual, one had 0.2 ppm. Since I was there two weeks ago they have replaced the chlorinator (the last one stopped working). Today Anne is getting the required NSF Approved sodium hypochlorite-- she was not aware that they were still using household bleach. Anne will be monitoring to determine that the chlorine residual is 1.0 ppm as we require. Additionally I told Anne that Boil Water Order would continue until at least the 1.0 ppm chlorine residual is consistent and samples are good.Since they are on a boil water order repeat sampling is not needed ACTION NEEDED: 1. Obtain and use correct hypochlorine solution.2. Assure that chlorinator pump is working.3. Maintain Free Chlorine residual at 1.0 ppm4. Daily check chlorine residual and record test results, send results to state.5 Take five temporary routine samples during October 2014.
 
Associated Alerts: COLI13358 - 10/01/2014 - COLIFORM (TCR)



More information for this water system: SDWIS ID 32
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login