OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90234
PWS Name: SMITH FROZEN FOODS INC
 
Who Was Contacted and Phone: Jake Divine
Contact Date: 07/15/2015
Contacted By: GARD, JEFF (DEPT OF AGRICULTURE)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: RP Sample Type Total Coliform positive-- sample date 6/25/2015. DETAILS: The set of repeat samples collected within 24 hours came back positive for total coliform. Coliform fact sheet sent to firm. A triggered source samples of Wells 2 and 3 were collected and both samples came back clean for coliforms. The firm will be collecting five routine samples in the last week of July. The firm will inform Drinking Water Department when additional water samples show no coliform bacteria. It appears the problem is not coming from the wells themselves but somewhere in the distribution system. A draft public notice was sent to the firm to be posted within 24 hours ACTION NEEDED: A triggered source sample must be collected. This requirement is to test the untreated source water (from a well) for coliform when "triggered." The trigger is a positive (present) result from a routine coliform sample in the distribution system. The water system has been disinfected and entire system has been flushed. Coliform fact sheet sent to firm. The firm must collect five routine samples in the month of July, preferably first week. A draft public notice was sent to the firm to be posted within 24 hours. A copy of the posted public notice is to be sent to DWS.
 
Associated Alerts: coli14292 - 06/30/2015 - COLIFORM (TCR)

coli14292 - 06/30/2015 - COLIFORM (TCR)

coli14292 - 06/30/2015 - COLIFORM (TCR)

coli14292 - 06/30/2015 - COLIFORM (TCR)



More information for this water system: SDWIS ID 2172
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login