OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00452
PWS Name: LAFAYETTE, CITY OF
 
Who Was Contacted and Phone: Jim Anderson (503) 864-3119
Contact Date: 09/03/2015
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Coliform
 
Details: SUMMARY: Total Coliform Positive Routine Sample DETAILS: I received an alert for a total coliform positive routine sample taken 8/28/15. Jim Anderson left a message on 8/31/15 while I was out of the office. I spoke to Jim Anderson on 9/1/15 when Jim called to discuss the repeat sampling requirements. He explained that he had already taken 3 repeat samples on 8/31/15, but was unclear what additional sampling was needed. I explained that 3 repeat samples was sufficient. We received the repeat sample results on 9/2/15. I realized on 9/3/15 that triggered source samples would be needed from the City of Dayton, which supplies Lafayette with groundwater. I called Scott Pingel with the City of Dayton and notified him of the sampling and he contacted Jim Anderson to complete the sampling. Jim and I spoke and Jim agreed that on 9/4/15 he would collect a triggered source sample from each of wells 1-5 that supply EP-D for the City of Lafayette. ACTION NEEDED: a triggered source sample needs to be taken from each of wells 1-5 from the City of Dayton. 5 temporary routine samples need to be taken from the City of Lafayette in the month of October. Provided all temporary and triggered samples are absent of bacteria, normal sampling can resume beginning in November.
 
Associated Alerts: COLI14594 - 08/31/2015 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4296
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login