OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 01072 | ||
PWS Name: | JOHNSON CREEK WATER SERVICE | ||
Who Was Contacted and Phone: | Aaron Olsen (503) 554-8333 | ||
Contact Date: | 09/30/2015 | ||
Contacted By: | BURNS, LAURA C (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | SURVEY/DEFICIENCY FOLLOW-UP | ||
Reasons: | SWTR Operations |
||
Details: | SUMMARY: new contact time DETAILS: Information provided by Aaron Olson: “The pump runs for 18 minutes at 125 gpm, then rests for 12 minutes before the pump starts again. Averaging a constant flow of 75 gpm.”Calculation:30 minutes total cycle-- 18 minutes on-- 12 minutes off.18 min “on” x 125 gal/min =2250 gal/cycle9,620gal = 4.27 cycles to move water to 300,000 gal tank. 2250 gal/cycle 4.27 cycles x 30 minutes = 128 minutes contact timeJohnson Creek should now use 128 minutes for the CT calculations beginning October 1, 2015. ACTION NEEDED: None. |