OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90556
PWS Name: TRIANGLE LAKE HIGH/ELEM SD 90
 
Who Was Contacted and Phone: Jeff Richardson/James Brookins (541) 925-3262
Contact Date: 10/07/2015
Contacted By: PULS, SARAH (LANE COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: Copper exceedance in Distribution DETAILS: Consulted with Jay McPherson regarding the next step for the water system since they are already on CC. Jay suggested the increase there minimum pH from 7.2 to 7.5, and to additionally monitor for alkalinity and temp. It was also suggested they make sure there pH meter was calibrated appropriately. ACTION NEEDED: Increase L & C sampling to 6 months, increase minimum pH to 7.5 and include alkalinity and temp when taking pH for data to determine what the new minimum pH level should be permanently.
 
Associated Alerts: CHEM6897 - 10/05/2015 - COPPER SUMMARY



More information for this water system: SDWIS ID 700
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login