OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 95484 | ||
PWS Name: | FIRST STOP MART | ||
Who Was Contacted and Phone: | Shelby Rothrock (541) 558-9411 | ||
Contact Date: | 10/08/2015 | ||
Contacted By: | GARD, JEFF (DEPT OF AGRICULTURE) | ||
Contact Method/Location: | Office | ||
Assistance Type: | WATER QUALITY ALERT RESPONSE | ||
Reasons: | Coliform N/A |
||
Details: | SUMMARY: Total Coliform positive-- sample date 10/06/2015. DETAILS: Routine sample for Total Coliform resulted in positive. The well is located in parking lot and store manager believes well was possibly hit by vehicle resulting in sediment falling into well. Sample site was at hand wash sink. Went over how to eliminate coliforms from well. Table Rock Analytical Laboratory will be collecting the four repeat samples within 24 hours. ACTION NEEDED: When a routine sample is total coliform-positive, a set of repeat samples must be collected within 24 hours of being notified of the positive results by the certified laboratory. Systems which collect one routine sample/month or less must collectat least four repeat samples for each total coliform-positive sample found. The systemmust collect at least one repeat sample from the sampling tap where the original total coliform -positive sample was taken , and at least one repeat sample at a tap within five service connections upstream and at least one repeat sample at a tap within five service connections downstream of the original sampling site. In short, three distribution and one triggered source sample. All repeat samples must be collected on the same day. Additionally, the firm must collect five routine samples the monthfollowing the routine present sample regardless of whether an MCL violation occurred or if repeat sampling was absent. | ||
Associated Alerts: | COLI14806 - 10/08/2015 - COLIFORM (TCR) |