OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00041
PWS Name: AMITY, CITY OF
 
Who Was Contacted and Phone: Matt Johnson (971) 237-6683
Contact Date: 02/03/2016
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Lead or Copper
Lead/Copper
 
Details: SUMMARY: Lead pigtail removal and consumer notification DETAILS: On 1/26/16 I sent Matt AWWA and EPA guidance on communication and messaging on lead service lines and advised him to investigate total replacement options if the whole service line was lead and told him that resampling needed to be done within 72 hours after a partial lead line removal. On 2/2/16 I was notified the results at 415 Nursery St from sampling conducted 1/27/16 were 0.0015 mg/l for lead and 0.188 mg/l for copper. The homeowner had asked Matt if they should not drink the water until the lead pigtail was replaced. I told Matt that there was nothing to indicate that the water is unsafe to drink at this time. This was based on the fact that the lead pigtail and service line had not been disturbed and the results were well below the lead and copper action levels. I told Matt that once the lead pigtail was replaced, the resident should not drink the water until the follow-up testing is completed showing lead and copper levels were below the Action Levels. I told Matt that the follow-up sampling should be conducted using the normal first draw sample after a tap had been unused for at least 6 hours and that if the homeowner was agreeable, the lead pigtail could be removed earlier than the 45-day notification of removal period had ended. ACTION NEEDED: System to collect tap sample within 72-hrs after removal of lead pigtail, provide appropriate notification to the resident. System also instructed to conduct a new materials evaluation to identify 20 Tier 1 sampling sites. System to remain on 6-month monitoring after copper Action Level exceedance from November 2015 sampling.


More information for this water system: SDWIS ID 4688
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login