OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00252
PWS Name: DAYTON, CITY OF
 
Who Was Contacted and Phone: Gary VanDerVeen (503) 434-7439
Contact Date: 02/17/2016
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: GWR
GWR
 
Details: SUMMARY: 4-LOG Treatment Confirmed DETAILS: System had a confirmed e-coli in sampling completed in July 2011 at the common header for the lower spring area A (SRC-AA) and the upper spring area B (SRC-AB). City reconstructed springs and installed 4-log viral disinfection treatment under PR#51-2013, which was granted Final Approval in a letter dated 1/31/14. The 1/31/14 letter specified they have to meet a minimum residual of 0.6 mg/l for combined spring flows up to a max of 80-gpm as measured after the 8-inch spring pipline during peak flow conditions. City started GWR Compliance Monitoring 3/1/14. ACTION NEEDED: City to continue daily compliance monitoring demonstrating that they meet a minimum entry point residual of 0.6 mg/l for 4-log viral disinfection of the combined spring flows up to a maximum of 80-gpm as measured after the 8-inch spring pipeline during peak flow conditions.
 
Associated Alerts: COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI

COLI9431 - 07/27/2011 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 4135
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login