OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90556
PWS Name: TRIANGLE LAKE HIGH/ELEM SD 90
 
Who Was Contacted and Phone: ALG lab report
Contact Date: 07/13/2016
Contacted By: MACPHERSON, JAMES (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
Operations
 
Details: SUMMARY: pH minimum is not met DETAILS: Lab staff measured pH in field at entry point, cafeteria, and gym. Readings were 5.97, 6.20, and 5.98, respectively, and confirmed by lab values. Thus, corrosion control treatment is not being operated correctly. This puts into question whether past readings from PWS are accurate, and thus a pH of 7.2 may in fact be adequate for optimal corrosion control. ACTION NEEDED: Lane County to query operator about pH measurements accuracy.
 
Associated Alerts: n/a - -