OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00194 | ||
PWS Name: | CLATSKANIE, CITY OF | ||
Who Was Contacted: | Daniel Smith | ||
Contact Phone: | 503-741-0799 | ||
Contact Date: | 05/07/2021 | ||
Contacted By: | SALIS, KARI (DWP) | ||
Contact Method/Location: | Phone | ||
Assistance Type: | OTHER REGULATORY - SCADA trending failure | ||
Reasons: | SWTR |
||
Details: | Daniel called to report that in the process of upgrading their PLC the trending function on their SCADA went out. He has been checking the individual filters and combined turbidity and chlorine manually every 4 hours (he can log on to the system remotely to check it). His alarms are still functional and are set at 0.1NTU on CFE (would automatically filter to waste until and operator put it in backwash mode), and 0.3 NTU for IFE. These alarms will ensure they will remain in compliance and the water produced will meet standards. He hopes to get it fixed today. |