OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00473
PWS Name: LEBANON, CITY OF
 
Who Was Contacted: Chris Germond
Contact Phone: 541-258-4274 (Email address hidden)
Contact Date: 05/20/2020
Contacted By: BAIRD, GREGG (DWP)
Contact Method/Location: Email
 
Assistance Type: OTHER WATER QUALITY - UCMR4 Manganese result
Reasons: Other
 
Details: Chris notified OHA about a UCMR4 manganese result of 520 ug/L collected on 5/5/20 from finished water at EP-B. This result is above the EPA lifetime/acute infant drinking water health advisory of 300 ug/L. OHA advised Lebanon to collect another finished water sample asap and have it analyzed for manganese at an accredited lab. Raw and finished water samples were collected 5/21/22; raw was 159 ug/L and finished water was non-detect. Chris indicated he would obtain a test kit and also do quarterly monitor at the lab while they investigated potential causes; he suspected either high river flows or membrane cleaning process-related (he indicated he would target sampling for after the cleaning process to see if related). A finished water sample collected 7/21/20 was 275 ug/L, just below the health advisory level, however all finished water testing after that (Sept 2020, Oct 2020, Feb 2021, April 2021) has been non-detected. A previous UCMR4 sample collected prior to the high result on 1/7/20 was very low at 1.7 ug/L and a subsequent UCMR4 sample collected 10/26/20 was also very low at 1.3 ug/L. Lebanon indicated they would continue quarterly monitoring to ensure finished water manganese levels remain below the health advisory level.


More information for this water system: SDWIS ID 3893
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login