OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05592
PWS Name: BOB BELLONI RANCH
 
Who Was Contacted: JAMES PINSON
Contact Phone: 541-396-5531
Contact Date: 05/17/2021
Contacted By: DOWNS, KENT (DWP)
Contact Method/Location: Phone
 
Assistance Type: OTHER REGULATORY - Zero chlorine residual reported in the surface water quality data form on 04.23.21
Reasons: SWTR
 
Details: Zero chlorine residual reported in the surface water quality data form on 04.23.21.

On 05.17.21 I contacted Jim. He stated that chlorine residual was measured first thing in the morning on 4/23/21. The issue that caused chlorine residual was identified and resolved within two hours.

What caused the issues: Apparently the filters were fouled and not allowing enough water for the post-filter pump to work. When flow is less than 3 gpm the pump stops working. With the pump down chlorine level dropped eventually to zero.

Corrective Action: The filters were replaced, the post-filter pump turned back on and the chlorine dose temporarily increased. Several water faucets in the distribution system were left open until chlorine residual was back to 0.2 ppm. After minimum required chlorine concentration was measured, the chlorine pump rate was set back to normal.

The operator forgot to record the corrected chlorine concentration and CT value once the level was back to 0.2 mg/ L.

A tier 2 public notice is not required.


More information for this water system: SDWIS ID 3924
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login