OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05246
PWS Name: PGE BEAVER GENERATING STATION
 
Who Was Contacted and Phone: Wayne Law (503) 728-7211
Contact Date: 02/16/2017
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: Follow up to 3Ts tap lead and copper sampling DETAILS: Wayne emailed me follow up lead and copper 250 mL sampling results taken under the 3Ts protocol (first draw and after 30 sec. of flushing) since the September 2016 initial 3Ts sampling from all fixtures. Results from fixtures in the maintenance lunchroom and steam turbine exceeded the threshold of 20 ppb lead in the 3Ts EPA guidance. Beaver has either replaced fixtures or installed filters at all high locations, and retested with results below 20 ppb lead. At one location in the steam turbine (utility sink) Beaver has posted a do not drink notice for high results. ACTION NEEDED: No further action needed at this time. 3Ts samples not used for lead and copper rule compliance with public water system sampling, as 1-Liter samples not collected. DWS to discuss results and ongoing PWS LCR sampling compliance as well as review tiered site selection criteria during 2017 water system survey.


More information for this water system: SDWIS ID 4162
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login