OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00792
PWS Name: SCAPPOOSE, CITY OF
 
Who Was Contacted and Phone: Darryl Sykes (503) 543-7185
Contact Date: 05/31/2017
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: IOCs
Operations
 
Details: SUMMARY: Follow up on fluoride split sample discrepency DETAILS: Discussed 2nd quarter fluoride split sample results with Darryl. The Citys fluoride sample was off by more than 30 % from the DEQ split sample: City at 0.51 mg/L and DEQ lab at 0.2 mgL. Darryl indicated that City is using a new spectophrotometer method, TNT 878. City discussed with Hach company, manufacturer of unit, that both the zero and test sample need to both be at room temperature when analyzed, which was not the case in this recent instance. City will wait and allow the test sample to warm to room temperature prior to conducting the next sample, so it matches zero sample temperature. City ordering fluoride calibration standard from Hach. ACTION NEEDED: City to conduct analysis according to instrument guidelines. City will conduct another split sample analysis with DEQ lab in July 2017 (3rd quarter) to see if the results are within 30% of each other (maximum allowed discrepency). 9/20/17 update: After 3rd quarter split samples are more than 30% off, Darryl indicated that in addtion to above, City has ensured consistent glassware, and through discussions with Hach is confident in their sample analysis technique. City will work with DEQ to further review analysis technique, to try and bring split samples within 30%. 11/29/17 update: Darryl indicated 4th qtr DEQ split was 0.68 and the City was 0.66 mg/L fluoride, well within the acceptable range.


More information for this water system: SDWIS ID 3908
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login