OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 93596
PWS Name: BEST WESTERN PIER POINT INN
 
Who Was Contacted and Phone: Tony Church (541) 997-7191 ext. 302
Contact Date: 09/11/2017
Contacted By: PULS, SARAH (LANE COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Source Confirmation Samples E.coli+ DETAILS: Five of the samples came back coliform positive with one being E.coli positive as well. Tony Church with Pier Point said he looked to see if any temporary sources of contamination could be possible and did not find anything out of the ordinary. The water system is an old spring located somewhere along the hillside by the hotel and it is piped into two cisterns that were installed in 1974. No one knows where the spring source location is exactly. The system practices chlorination at high levels normally from 1.0 to 2.0 and they also record it daily. Phebe Howe did a contact time calculation that shows the system only needs to maintin a 0.2 ppm to achieve 4-log disinfection in the water system. No boil water notice needs to be issued, system is performing interim 4-log disinfection. ACTION NEEDED: Wait for corrective action based on a source assessment.
 
Associated Alerts: COLI17126 - 09/11/2017 - COLIFORM (TCR) , E. COLI

COLI17126 - 09/11/2017 - COLIFORM (TCR) , E. COLI

COLI17126 - 09/11/2017 - COLIFORM (TCR) , E. COLI

COLI17126 - 09/11/2017 - COLIFORM (TCR) , E. COLI

COLI17126 - 09/11/2017 - COLIFORM (TCR) , E. COLI

COLI17126 - 09/11/2017 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 1387
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login