OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00586 | ||
PWS Name: | ODELL WATER COMPANY | ||
Who Was Contacted and Phone: | Phil Davis (541) 354-1885 | ||
Contact Date: | 05/10/2017 | ||
Contacted By: | CIVIL WEST ENGINEERS, INC (DWP) | ||
Contact Method/Location: | Field | ||
Assistance Type: | CIRCUIT RIDER ASSISTANCE | ||
Reasons: | N/A N/A |
||
Details: | SUMMARY: MPA Sampling DETAILS: Circuit Rider installed MPA filter apparatus on the afternoon of May 15th. Apparatus was disconnected on the morning of May 16th. Approximately 1000 gallons had passed through filter. Filter was shipped to the Grants Pass Water Laboratory, and was received there on May 17th. Results of analysis are attached. Water scored a 2 out of 100 and was labeled as “low risk” of being under the influence of surface water at the time of the sampling. ACTION NEEDED: None. |