OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00042
PWS Name: ANTELOPE, CITY OF
 
Who Was Contacted: Code Flecker
Contact Phone: 928-502-1348 (Email address hidden)
Contact Date: 08/05/2021
Contacted By: BAILEY, NICOLE (WASCO COUNTY)
Contact Method/Location: Phone
 
Assistance Type: OTHER REGULATORY - New water system operator, talked about chlorine
Reasons: Operations
 
Details: The reason for my contact with Antelope this morning was originally prompted by a phone call I received regarding a concerned citizen in Antelope who noted very strong chlorine levels in their tap water.

The new water system operator is the Water Master for Antelope, Cody Flecker.
Rodney Shanks is the mayor now, and the phone number I had for Peggy Sue is no longer in service. I will change the contacts I have for this system.

I noted that we currently do not have a total coliform sample reported for July.
Box R Water performs Antelope's water system sampling and turns them in, and Cody said he would check up with them on turning in samples late in the month.
I advised that taking samples late in the month does not offer the flexibility of if the sample couldn't be taken on the last week due to unforeseen circumstances. Box R Water may also be able to provide some information on if they have chlorine residuals noted from when they took heir monthly coliform sample.

I asked him if he takes chlorine residual tests and Cody said he does it three times a week at the post office in town. I asked him what the ideal was or if he had a number given by the kit. He mentioned it's usually around a 1.0 and I advised we should work to find a ratio that is closer to 0.40-0.20. Cody uses a Hach test kit with Dpd tablets to test chlorine residuals, which is an approved testing method.

I requested that he adjust the chlorine injector to a lower setting, and then subsequently check several locations in town what the chlorine residual is. I also requested that he document every chlorine residual he samples.

We spoke about using chlorine that Antelope is using. He noted that they are using regular bleach which as of several years ago is no longer approved due to most commercial bleaches not getting NSF Certified. He called me back and had found a NSF 60 rated bleach online, but would go through Maupin Stoves and Spas to source NSF chlorine.




More information for this water system: SDWIS ID 3224
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login