OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01092
PWS Name: USFS TILLER RANGER STATION
 
Who Was Contacted: Jonathan Woody
Contact Phone: 541-643-6137 (Email address hidden)
Contact Date: 07/20/2021
Contacted By: TEMPLIN, REBECCA (DWP)
Contact Method/Location: Email
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
 
Details: Reached out to Jonathan Woody to discuss the high result for TTHM disinfection byproducts (TTHM = 0.1170 mg/L). USFS Tiller Ranger Station is working on operational changes to lower the TTHM levels in the water. They have started flushing monthly, reduced the reservoir levels and reduced the chlorine dosage. The HAA5 levels have been reducing, but there is still problems with the TTHM levels. The system is going to clean the tanks, install and auto-flush system, and move to post-chlorination instead of pre-chlorination.
 
Associated Alerts: CHEM9379 - 07/13/2021 - TOTAL TRIHALOMETHANES (TTHM)



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 4008