OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 00554 | ||
PWS Name: | NEHALEM, CITY OF | ||
Who Was Contacted: | Don Davidson | ||
Contact Phone: | 503-801-0955 | ||
Contact Date: | 06/14/2021 | ||
Contacted By: | CIVIL WEST ENGINEERS, INC (DWP) | ||
Contact Method/Location: | Field | ||
Assistance Type: | CIRCUIT RIDER ASSISTANCE | ||
Details: | Background/Problem Identification: The water system has added a solar-bee mixer and wishes to have a CT study done to determine the effect the new mixer is having on the contact time. Assistance Provided: The methodology has been created and approved by OHA. A tracer test was attempted on 02/25/21. During the test, the operator turned off the chlorinator due to fears that the residual to distribution would be too high. There is a process chlorine meter that has historically shown wildly high readings, normally 20 ppm, these readings had climbed to 60 ppm during the test. Lack of continued communication has resulted in this support being closed Follow-Up Actions Needed: Once the problem chlorine meter addressed then they can re-run the tracer test. Technical Reports to be Prepared and Expected Timeframe: N/A |