OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00725
PWS Name: MCNULTY WATER PUD
 
Who Was Contacted: Robert Trotter
Contact Phone: 971-832-9148
Contact Date: 11/30/2021
Contacted By: OSBORN, DANIEL (COLUMBIA COUNTY)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: I spoke with Robert Trotter regarding McNulty Water PUD's two recent Repeat coliform sample results off Morse Rd and Millard Rd. Robert said he plans to shock chlorinate the water line in that region, to about a concentration of 1.0 mg/L. Robert said he will contact all the households on that line and let them know he is about to shock that line in advance.
He is coordinating this shock chlorination by hooking up the chlorination system at a vacant home on the line, and then isolating that line, making it a one-way line through the fire hydrant to prevent the chlorination to continue on to the rest of the distribution system.
This is done to target that area that seems to have this issue; as the recent repeat positive samples were also at locations near the previous positive coliform sample results took place.
Robert then added that after leaving the line shock chlorinated overnight, he plans to flush out the line the next day. And then after the flushing occurs, he plans to let the water sit for 24 hours and then collect some special samples representative of that water line.
A Level 2 Coliform Investigation was already conducted at McNulty Water PUD on 11/23/2021.
 
Associated Alerts: COLI21696 - 11/29/2021 - COLIFORM, TOTAL (TCR)



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3402