OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00725
PWS Name: MCNULTY WATER PUD
 
Who Was Contacted: Robert Trotter
Contact Phone: 971-832-9148
Contact Date: 11/30/2021
Contacted By: OSBORN, DANIEL (COLUMBIA COUNTY)
Contact Method/Location: Phone
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
 
Details: I spoke with Robert Trotter regarding McNulty Water PUD's two recent Repeat coliform sample results off Morse Rd and Millard Rd. Robert said he plans to shock chlorinate the water line in that region, to about a concentration of 1.0 mg/L. Robert said he will contact all the households on that line and let them know he is about to shock that line in advance.
He is coordinating this shock chlorination by hooking up the chlorination system at a vacant home on the line, and then isolating that line, making it a one-way line through the fire hydrant to prevent the chlorination to continue on to the rest of the distribution system.
This is done to target that area that seems to have this issue; as the recent repeat positive samples were also at locations near the previous positive coliform sample results took place.
Robert then added that after leaving the line shock chlorinated overnight, he plans to flush out the line the next day. And then after the flushing occurs, he plans to let the water sit for 24 hours and then collect some special samples representative of that water line.
A Level 2 Coliform Investigation was already conducted at McNulty Water PUD on 11/23/2021.
 
Associated Alerts: COLI21696 - 11/29/2021 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3402
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login